| Catalogue Sheet Set valid since 1 Nov. 2004 version ČSN EN 13501-2 |
E(I) 15 - 120 |
06 | 06402 |
Caution: these pages serve only for the first information about material for designers and investors, they are solved in one uniform chart and they don't pose pretentions on perfections. Other basis or details can be found out in our technical office. Data written in this list agree with by this time publicated data and obtained experience of J.SEIDL a spol.., s.r.o. Supplier is not in charge of applications done out of frame here given tests and certifications - operations of fire fighting applications with product mentioned in this list without written authorisation of producer or author are prohibited.
Product Catalogue Sheet
The bonded fillers for both expanding and stable construction joints in vertical antifire partitioning structures, securing their fire resistance in compliance with the ČSN 73 0810 due to ČSN EN 13501-2. The systems are formed based on plates from ORSIL PYRO mineral fibres and the fire-resistant glue with intumescent paints, are without any asbestos, halogens and heavy metals.
Exterior: Grey-green and grey-brown plate elements, set before the joint hole in the antifire partitioning structure. These elements cover the joint hole completely. The fillers allow expanding movements of joints within the prior set extent.
The system is to be applied for fillers of construction joints in vertical antifire partitioning structures, both fixed and expanding, and the fire resistance between E(I) 30 and E(I) 120 in compliance with the ČSN EN 13501-2 may be achieved by them.
The fillers are suitable for:Industrial environments with the industrial atmosphere to degree IV and for all common heated and non-heated interiors. The fillers are not of any load for the structure, are without any cracks, and may withstand any vibrations and dynamic shocks very well.
The fillers are not suitable for: Environments with strong corrosivity (pH, aromats and organic fumes) and for places with flowing or dropping water, respectively for non-ventilated places with the rel. air moisture higher than 90 %.
References to concrete certificates are given in the Supplement to this Catalogue Sheet
All deliveries of these systems shall be executed by J.SEIDL & spol.,s.r.o., being the owner of the know-how and of all industrial rights, and where any requests and tested sorts of fillers may be sent .
When commonly used as for the constructions and the environment in compliance with par. B and under observation of prescribed technological procedures, the fillers shall meet the provisions set under § 47 par. 1 of the Building Act for the period of the economic life of the structure, with the exclusion of any mechanical damage.
The ORDEXAL® antifire fillers for construction joints were tested with evidence by the accredited PAVÚS - Veselí n.L. Testing Agency and certified by the AO 216 Praha.
Based on the said tests and records this body executed Records on Specification with the computed values of fire resistance as for different kinds of structures concerning their various antifire properties. The Table gives the set of individual filler and specifications thereof as follows.
| Product and number of Records on Specification certificate number |
Identification of filler type |
Filler specification Due to ČSN EN 13501-2 |
| ORDEXAL® WP-1 PK2-12-04-001-C-0 0234/216/§5/2004 |
ORDEXAL® WP-J-1/2S ORDEXAL® WP-J-NS-V |
E 120/EI 30-V-X-F-W00 to 60 (vz. 01-02) E 120/EI 45-T-X-F- W00 to 60 (vz. 10) |
| ORDEXAL®WP-O-S |
EI 120-T-X-F-W00 to 60 (vz. 07) | |
| ORDEXAL® P-1 PK2-12-04-001-C-0 0234/216/§5/2004 |
ORDEXAL® P-J-1/2S ORDEXAL® P-J-1/2V |
E 120/EI 45-VT-X-F-W00 to 60 (vz.03-04,08-09) |
| ORDEXAL®P-O-S ORDEXAL® P-O-V |
EI120-VT-X-F-W00 to 60 (vz. 05-06) |
|
| ORDEXAL® U PK2-12-04-001-C-0 0234/216/§5/2004 |
ORDEXAL® UJNS ORDEXAL® UO |
E 90/I60-V-X-W00 to 40 EI90-V-X-W00 to 40 |
Explanations to individual fillers:
WP - without paint,
P - painted,
J -with lining on one side,
O - on both sides,
1/2 - out of any side,
NS - non-heated side
V - horizontally,
S - vertically - U - inside
The application of any system shall always be bound with observation of the prescribed know-how and keeping the precise material composition in compliance with the samples tested by the PAVÚS Veselí n.L ,Testing Agency as well as with valid certificates. Therefore, only the firms that may submit the written authorization, and were trained by J.Seidl & spol.,s.r.o., (being in possession of all industrial right to this application) may execute these applications. Should this condition be not met, then, the Certificate, respectively the Declaration of Compliance, may not be applied for any executed work.
ČSN series 73 08 02, 04, 10 and other relating des.. norms, ČSN EN 1363-1, ČSN EN 13501-2; ČSN EN 1366-1, certificates, technical supporting documents and other documents from producers and from J.Seidl & spol.,s.r.o.
Sídlo společnosti:
J Seidl a spol., s.r.o. Husova 120,
544 01 Dvůr Králové nad Labem,
tel: 499 320 459, fax: 499 320 219
Technická kancelář:
Pražská 16, 102 21 Praha 10,
tel/fax: 281 017 369, mobil: 608 075 005,
e-mail: bohuslav@seidl.cz, web: www.seidl.cz
VOR-KOS v Hradci Králové, oddíl C, vložka 4,
bankovní spojení KB Trutnov 13443/601/0100
IČ: 00484016
© J. Seidl & spol., s.r.o. 2009
Realizace www stránek: Saturn-Toya